Analysis of the deformed condition of a residential building damaged as a result of hostilities

UDC: 622.837:622.838
DOI: 10.24412/1996-885X-2023-2237-72-83
EDN: CIDSXS
Received: 03.10.2023
Published: 17.10.2023

Original language: ru

JATS XML

Ivanova Larisa Aleksandrovna, Candidate of Technical Sciences, FSBSI «RANIMI», Senior Researcher of the Department of Displacement of the Earth’s Surface and Protection of Undermined Objects, email: ivlarisa213@yandex.ru
Rakhmanova Tatiana Ivanovna, FSBSI «RANIMI», Senior Researcher of the Department of Displacement of the Earth’s Surface and Protection of Undermined Objects, email: rahmanovatata@yandex.ru

Abstract
Based on the analysis of design features and the results of the survey of a residential building on Pinter Street, 8 in Donetsk, which received structural damage as a result of hostilities, it was established that: the technical condition of the structures of the first entrance is limited operational, on the ninth, technical floors and roof is emergency; the technical condition of the structures of the second entrance is emergency. Measures have been developed for the further use of the residential building.

Keywords: residential building survey results, technical condition of structures

Funding
The research has been completed within the framework of the state assignment of the Ministry of Science and Higher Education of the Russian Federation (1023020700011-0-2.7.5).

REFERENCES
  1. Правила подработки зданий, сооружений и природных объектов при добыче угля подземным способом: ГСТУ 101.00159226.001 – 2003. – Введ. 01.01.2004. – К., 2004. – 128 с.
  2. Здания и сооружения. Правила обследования и мониторинга технического состояния: ГОСТ 31937 – 2011. – Введ. 2014-01-01. – М.: Изд-во стандартов, 2014. – 55 с.
Мы используем файлы cookie и рекомендательные технологии. Пользуясь сайтом, вы соглашаетесь с Политикой обработки персональных данных.
Принять
Политика конфиденциальности